STATIC PRESSURE DIAGNOSTIC

Penguin Air & Plumbing - Interactive Field Tool

Version 4.4

Job Information

From the equipment data plate. Usually 0.50.

Both Zones Calling

Enter as positive (gauge reading)
Enter as positive (gauge reading)

Zone 1 Only (Zone 2 Closed)

Zone 2 Only (Zone 1 Closed)

Pressure Budget Analysis

Zoning Problem Check

Bypass Damper Sizing

If zoning problem exists (TESP jumps >0.2"), bypass damper is needed
Read from furnace blower curve at the high TESP value

DAT Sensor (Freeze Protection)

DAT = supply air TEMPERATURE sensor (not pressure). When supply air gets too cold (coil freezing risk), it triggers a purge cycle: compressor/furnace OFF, fan ON only, until coil warms. Then restarts.

When to Recommend DAT Sensor

Always recommend DAT sensor on zoned Honeywell systems

Especially important if: TESP jumps above 0.7" when a zone closes (creates high supply velocity and coil freezing risk)

Field Notes